- Recruitment
- Right people for NSV
- NSV PEOPLE
- Task
- HR System Welfare
Type | Power and capacity |
Revolution per minute |
Installation location | Remarks | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Slab on Grade | Floor span | |||||||||||||||
Up to 6m | 6 to 9m | 9 to 12m | ||||||||||||||
Base Type |
Isolator Tye |
Min Defl., mm |
Base Type |
Isolator Tye |
Min Defl., mm |
Base Type |
Isolator Tye |
Min Defl., mm |
Base Type |
Isolator Tye |
Min Defl., mm |
|||||
Refrigeration Machines and Chillers |
Reciprocating | All | All | A | 2 | 6.4 | A | 4 | 19 | A | 4 | 38 | A | 4 | 64 | 2,3,12 |
Centrifugal, Scroll |
All | All | A | 1 | 6.4 | A | 4 | 19 | A | 4 | 38 | A | 4 | 38 | 2,3,4,8,12 | |
Screw | All | All | A | 1 | 25 | A | 4 | 38 | A | 4 | 64 | A | 4 | 64 | 2,3,4,12 | |
Absorption | All | All | A | 1 | 6.4 | A | 4 | 19 | A | 4 | 38 | A | 4 | 38 | ||
Air Cooled recip., Scroll |
All | All | A | 1 | 6.4 | A | 4 | 38 | A | 4 | 38 | A | 4 | 64 | 2,4,5,12 | |
Air Cooled Screw |
All | All | A | 4 | 25 | A | 4 | 38 | B | 4 | 64 | B | 4 | 64 | 2,4,5,8,12 | |
Air Compressors and Vacuum Pumps |
Tank-mounted hortz. |
≥ 7.5 | All | A | 3 | 19 | A | 3 | 19 | A | 3 | 38 | A | 3 | 38 | 3,15 |
≥ 11 | All | C | 3 | 19 | C | 3 | 19 | C | 3 | 38 | C | 3 | 38 | 3,15 | ||
Tank-mounted vert. |
All | All | C | 3 | 19 | C | 3 | 19 | C | 3 | 38 | C | 3 | 38 | 3,15 | |
Base-mounted | All | All | C | 3 | 19 | C | 3 | 19 | C | 3 | 38 | C | 3 | 38 | 3,14,15 | |
Large reciprocating |
All | All | C | 3 | 19 | C | 3 | 19 | C | 3 | 38 | C | 3 | 38 | 3,14,15 | |
Pumps | Close-coupled | ≥ 5.6 | All | B | 2 | 6.4 | C | 2 | 19 | C | 2 | 19 | C | 3 | 19 | 16 |
≥ 7.5 | All | C | 3 | 19 | C | 2 | 19 | C | 2 | 19 | C | 3 | 38 | 16 | ||
Large Inline | 37 to 19 | All | A | 3 | 19 | A | 3 | 38 | C | 3 | 38 | A | 3 | 38 | ||
≥ 22 | All | A | 3 | 38 | A | 3 | 38 | C | 3 | 38 | A | 3 | 64 | |||
End suction and split case |
≥ 7.5 | All | C | 3 | 19 | C | 3 | 19 | A | 3 | 38 | C | 3 | 38 | 16 | |
37 to 93 | All | C | 3 | 19 | C | 3 | 19 | A | 3 | 38 | C | 3 | 64 | 10, 16 | ||
≥ 110 | All | C | 3 | 19 | C | 3 | 38 | C | 3 | 64 | C | 3 | 89 | 10, 16 | ||
Packaged pump systems |
All | All | A | 3 | 19 | A | 3 | 19 | C | 3 | 38 | C | 3 | 64 | ||
Cooling Towers |
All | All | Up to 300 | A | 1 | 6.4 | A | 4 | 89 | C | 4 | 89 | A | 4 | 89 | 5, 8, 18 |
301 to 500 | A | 1 | 6.4 | A | 4 | 64 | A | 4 | 64 | A | 4 | 64 | 5, 18 | |||
501 to up | A | 1 | 6.4 | A | 4 | 19 | A | 4 | 19 | A | 4 | 38 | 5, 18 | |||
Bollers | Fire-tube | All | All | A | 1 | 6.4 | B | 4 | 19 | A | 4 | 38 | B | 4 | 64 | 4 |
Water-tube, copper fin |
All | All | A | 1 | 3 | A | 4 | 3 | B | 4 | 3 | B | 4 | 6.4 | ||
Axial Fans, Plenum Fans, Cabinet Fans, Fan Sections, Centrifugal, Inline Fans |
Up to 560mm, diameter |
All | All | A | 2 | 6.4 | A | 1 | 19 | B | 1 | 19 | C | 3 | 19 | 4,9 |
610mm diameter and up |
≥ 50 Pa SP | Up to 300 | B | 3 | 64 | C | 3 | 89 | A | 3 | 89 | C | 3 | 89 | 9,8 | |
301 to 500 | B | 3 | 19 | B | 3 | 38 | A | 3 | 64 | C | 3 | 64 | 9,8 | |||
501 to up | B | 3 | 19 | B | 3 | 38 | C | 3 | 38 | B | 3 | 38 | 9,8 | |||
≥ 501 Pa SP | Up to 300 | C | 3 | 64 | C | 3 | 89 | C | 3 | 89 | C | 3 | 89 | 3,8,9 | ||
301 to 500 | C | 3 | 38 | C | 3 | 38 | C | 3 | 64 | C | 3 | 64 | 3,8,9 | |||
501 to up | C | 3 | 19 | C | 3 | 38 | C | 3 | 38 | C | 3 | 64 | 3,8,9 | |||
Centrifugal Fans |
Up to 560mm, diameter |
All | All | B | 2 | 6.4 | B | 3 | 19 | C | 3 | 19 | B | 3 | 38 | 9,19 |
610mm diameter and up |
≥ 30 | Up to 300 | B | 3 | 64 | B | 3 | 89 | B | 3 | 89 | B | 3 | 89 | 8,19 | |
301 to 500 | B | 3 | 38 | B | 3 | 38 | B | 3 | 64 | B | 3 | 64 | 8,19 | |||
501 and up | B | 3 | 19 | B | 3 | 19 | B | 3 | 19 | B | 3 | 38 | 8,19 | |||
≥ 37 | Up to 300 | C | 3 | 64 | C | 3 | 89 | C | 3 | 89 | C | 3 | 89 | 2,3,8,9,19 | ||
301 to 500 | C | 3 | 38 | C | 3 | 38 | C | 3 | 64 | C | 3 | 64 | 2,3,8,9,19 | |||
501 and up | C | 3 | 25.4 | C | 3 | 38 | C | 3 | 38 | C | 3 | 64 | 2,3,8,9,19 | |||
Centrifugal Fans |
All | All | All | A | 1 | 6.4 | A | 4 | 19 | C | 4 | 38 | AVD | 4 | 38 | |
Centrifugal Fans |
All | All | All | A | 1 | 6.4 | A | 4 | 19 | C | 4 | 38 | AVD | 4 | 38 | |
Packaged AH, AC, H and V units |
All | ≥ 7.5 | All | A | 3 | 19 | A | 3 | 19 | A | 3 | 19 | A | 3 | 19 | 19 |
≥ 11 | Up to 300 | A | 3 | 19 | A | 3 | 89 | A | 3 | 89 | C | 3 | 89 | 2,4,8,19 | ||
≥ 1 kpa Sp | 301 to 500 | A | 3 | 19 | A | 3 | 64 | A | 3 | 64 | A | 3 | 19 | 4,19 | ||
501 and up | A | 3 | 19 | A | 3 | 38 | A | 3 | 38 | A | 3 | 38 | 4,19 | |||
> 1 kpa sp11 | Up to 300 | B | 3 | 19 | C | 3 | 89 | C | 3 | 89 | C | 3 | 89 | 2,3,4,8,9 | ||
> 1 kpa Sp | 301 to 500 | B | 3 | 19 | C | 3 | 38 | C | 3 | 64 | C | 3 | 64 | 2,3,4,9 | ||
501 and up | B | 3 | 19 | C | 3 | 38 | C | 3 | 38 | C | 3 | 64 | 2,3,4,9 |